Parameters
List of parameters
1-1014
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Values: 0: STOP A
1: STOP B
2: STOP C
3: STOP D
4: STOP E
5: Sets the stop response via p9563 (SLS-specific)
10: STOP A with delayed pulse cancelation when the bus fails
11: STOP B with delayed pulse cancelation when the bus fails
12: STOP C with delayed pulse cancelation when the bus fails
13: STOP D with delayed pulse cancelation when the bus fails
14: STOP E with delayed pulse cancelation when the bus fails
Dependency: Refer to: p9531, p9563, p9580
Note: A change only becomes effective after a POWER ON.
SLS: Safely-Limited Speed / SG: Safely reduced speed
Description: Sets the stop response for the function "Safely-Limited Position" (SLP).
Values: 2: STOP C
3: STOP D
4: STOP E
Dependency: Refer to: p9534, p9535
Note: A change only becomes effective after a POWER ON.
SLP: Safely-Limited Position / SE: Safe software limit switches
Description: Sets the SLS-specific stop response for the function "Safely-Limited Speed" (SLS).
These settings apply to the individual limit values for SLS.
Values: 0: STOP A
1: STOP B
2: STOP C
3: STOP D
4: STOP E
10: STOP A with delayed pulse cancelation when the bus fails
11: STOP B with delayed pulse cancelation when the bus fails
12: STOP C with delayed pulse cancelation when the bus fails
13: STOP D with delayed pulse cancelation when the bus fails
14: STOP E with delayed pulse cancelation when the bus fails
Index: [0] = Limit value SLS1
[1] = Limit value SLS2
[2] = Limit value SLS3
[3] = Limit value SLP4
Dependency: Refer to: p9531, p9561, p9580
Notice: Values 10 to 14 are being prepared and are presently ineffective.
p9562 SI motion SLP (SE) stop response (Control Unit) / SI Mtn SLP resp
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 4
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
2 4 2
p9563[0...3] SI motion SLS (SG)-specific stop response (Control Unit) / SI Mtn SLS stop
SERVO, VECTOR Can be changed: C2 Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 14 2