Parameters
List of parameters
1-136
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the rated motor power factor (cos phi, rating plate).
For a parameter value of 0.000, the power factor is internally calculated and displayed in r0332.
Dependency: This parameter is only available for IEC motors (p0100 = 0).
Refer to: p0100, p0309, r0332
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
The parameter is automatically preset for motors from the motor list (p0301).
Description: Sets the rated motor efficiency (rating plate).
For a parameter value of 0.0, the power factor is internally calculated and displayed in r0332.
Dependency: This parameter is only available for NEMA motors (p0100 = 1).
Refer to: p0100, p0308, r0332
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
The parameter is automatically preset for motors from the motor list (p0301).
Description: Sets the rated motor frequency (rating plate).
Dependency: The number of pole pairs (r0313) is automatically re-calculated when the parameter is changed (together with
p0311), if p0314 = 0.
Refer to: p0311, r0313, p0314
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is automatically pre-assigned for induction motors from the motor list (p0301).
For synchronous motors, the parameter is not required and must therefore be pre-assigned zero. For p0310 = 0, it
is not possible to calculate the pole pair; instead, it must be entered in p0314.
p0308[0...n] Rated motor power factor / Mot cos_phi_rated
SERVO, VECTOR Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
0.000 1.000 0.000
p0309[0...n] Rated motor efficiency / Mot eta_rated
VECTOR Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
0.0 [%] 99.9 [%] 0.0 [%]
p0310[0...n] Rated motor frequency / Mot f_rated
SERVO Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]