List of parameters
Parameters
1-289
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Runs the appropriate ACX file on the CompactFlash card.
The Connector Inputs (CI) for the velocity setpoints of the appropriate Command Data Set (CDS) are appropriately
interconnected.
The selected ACX file must be located in the following directory:
... /PMACROS/<drive object>/P1000/PMxxxxxx.ACX
Example:
p1000 = 6 --> the file PM000006.ACX is run.
Dependency: The ACX file to be run must be created according to the definition for ACX macros and must be saved in the direc-
tory intended on the CompactFlash card.
Refer to: p0015, p0700, p1500, r8572
Notice: No errors were issued during fast commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
Note: The macros in the specified directory are displayed in r8572. r8572 is not in the Expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
CI: Connector Input
Description: Sets a value for the fixed speed / velocity setpoint 1.
Dependency: Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice: A BICO interconnection to a parameter that belongs to a drive objects always acts on the effective data set.
Description: Sets a value for the fixed speed / velocity setpoint 1.
Dependency: Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice: A BICO interconnection to a parameter that belongs to a drive objects always acts on the effective data set.
p1000[0...n] Macro Connector Inputs (CI) for velocity setpoints / Macro CI v_set
SERVO (Lin) Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: CDS, p0170 Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 999999 0
p1001[0...n] CO: Fixed speed setpoint 1 / n_set_fixed 1
SERVO (Extended
setp), VECTOR
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 1021, 3010
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
-210000.000 [RPM] 210000.000 [RPM] 0.000 [RPM]
p1001[0...n] CO: Fixed velocity setpoint 1 / n_set_fixed 1
SERVO (Extended
setp, Lin)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 1021, 3010
P-Group: Setpoints Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
-1000.000 [m/min] 1000.000 [m/min] 0.000 [m/min]