List of parameters
Parameters
1-649
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the traversing distance for incremental jog 1.
Dependency: Refer to: p2585, p2589, p2591
Note: Incremental jog 1 is started with BI: p2591 = 1 signal and BI: p2589 = 0/1 signal.
With BI: p2589 = 0 signal, incremental jog is interrupted.
Description: Sets the traversing distance for incremental jog 2.
Dependency: Refer to: p2586, p2590, p2591
Note: Incremental jog 2 is started with BI: p2591 = 1 signal and BI: p2590 = 0/1 signal.
With BI: p2590 = 0 signal, incremental jogging is interrupted.
Description: Sets the signal source for jog 1.
Dependency: When jogging, the axis is accelerated or braked with the maximum acceleration/deceleration (p2572/p2573).
BI: p2591 = 0 signal
The axis endlessly moves with the setpoint velocity, jog 1 (p2585).
BI: p2591 = 1 signal
The axis traverses through a parameterized distance (p2585) with the setpoint velocity, jog 1 (p2587).
Refer to: p2572, p2573, p2585, p2587, p2591
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for jog 2.
p2587 EPOS jog 1 traversing distance / Jog 1 distance
SERVO (EPOS),
VECTOR (EPOS)
Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: - Func. diagram: 3610
P-Group: Basic positioner Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [LU] 2147482647 [LU] 1000 [LU]
p2588 EPOS jog 2 traversing distance / Jog 2 distance
SERVO (EPOS),
VECTOR (EPOS)
Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: - Func. diagram: 3610
P-Group: Basic positioner Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [LU] 2147482647 [LU] 1000 [LU]
p2589 BI: EPOS jog 1 signal source / Jog 1 S_src
SERVO (EPOS),
VECTOR (EPOS)
Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 3610, 3625
P-Group: Basic positioner Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p2590 BI: EPOS jog 2 signal source / Jog 2 S_src
SERVO (EPOS),
VECTOR (EPOS)
Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 3610, 3625
P-Group: Basic positioner Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0