Parameters
List of parameters
1-324
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the signal source for control word 1 bit 6 (enables setpoint/disable setpoint).
Dependency: Refer to: p1140, p1141
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 6 = 0: Inhibits the setpoint (the ramp-function generator input is set to zero)
Bit 6 = 1: Enable setpoint
Description: Sets the signal source for control word 1 bit 6 (enables setpoint/disable setpoint).
Dependency: Refer to: p1140, p1141
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 6 = 0: Inhibits the setpoint (the ramp-function generator input is set to zero)
Bit 6 = 1: Enable setpoint
Description: Sets the signal source for accepting the setting value of the ramp-function generator.
Dependency: The signal source for the ramp-function generator setting value is set using parameters.
Refer to: p1144
Note: 0/1 signal:
The ramp-function generator output is immediately (without delay) set to the setting value of the ramp-function gen-
erator.
1 signal:
The setting value of the ramp-function generator is effective.
1/0 signal:
The input value of the ramp-function generator is effective. The ramp-function generator output is adapted to the
input value using the ramp-up time or the ramp-down time.
0 signal:
The input value of the ramp-function generator is effective.
p1142[0...n] BI: Enable velocity setpoint / Enable v_set
SERVO (Lin) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2441, 2442,
2443, 2501, 2711
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1
p1142 BI: Enable speed setpoint / Enable n_set
TM41 Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 9674
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1
p1143[0...n] BI: Ramp-function generator, accept setting value / Accept RFG set val
SERVO (Extended
setp), VECTOR
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0