Note: When motor rating plate parameters are changed, the final display is reset. When setting the individual bits, all of
the most significant bits are reset.
Bit 00 = Complete calculation of the motor/control parameters (p0340 = 1, p3900 > 0).
Bit 02 = Motor data identification (p1910 = 1) successfully completed.
Bit 03 = Rotating measurement (p1960 = 1, 2) successfully completed.
Bit 04 = Motor encoder adjustment (p1990 = 1) successfully completed.
Bit 15 = Equivalent circuit diagram parameters of the motor were subsequently manually changed.
Description: Displays the data determined from the motor identification and that has been accepted.
Dependency: Refer to: r3925
Description: Successfully completed component of the last motor data identification carried out.
r3927[0...n] Motor data identification determined data (induction motor) / MotID det dat ASM
SERVO Can be changed: - Calculated: CALC_MOD_ALL Access level: 3
Data type: Unsigned32 Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 p0350 accepted Yes No -
01 p0354 accepted Yes No -
02 p0356 accepted Yes No -
03 p0358 accepted Yes No -
04 p0360 accepted Yes No -
05 p0320 accepted Yes No -
06 p0410 accepted Yes No -
12 p1715 accepted Yes No -
13 p1717 accepted Yes No -
14 p1590 accepted Yes No -
15 p1592 accepted Yes No -
22 p0341 accepted Yes No -
r3927[0...n] Motor data identification control word / MotID STW
VECTOR Can be changed: - Calculated: CALC_MOD_ALL Access level: 3
Data type: Unsigned16 Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Stator inductance estimate no measure-
ment
Yes No -
01 Cl.-loop current control w/ dead-beat con-
troller
Yes No -
02 Rotor time constant estimate no measure-
ment
Yes No -
03 Leakage inductance estimate no measure-
ment
Yes No -
04 Activates the identification dynamic leak-
age inductance
Yes No -
05 Determine Tr and Lsig evaluation in the time
range
Yes No -
06 Activates vibration damping Yes No -
07 De-activates the vibration detection Yes No -