Siemens SINAMICS S Series - p3463 Infeed, line angle change, phase failure detection; INF Phi phase fail; r3468[0...1] Infeed voltage alpha;beta line filter; INF V a;b filter; p3469[0...n] Latch delay time correction, zero crossover detection; t_latch corr PLL; r3470 Infeed active current filter; INF I_act filter

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-707
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: If the line supply angle (angle between the line supply phases) suddenly changes by this value, then a phase failure
is assumed. The pulses are then inhibited for 10 ms.
Dependency: Refer to: A06205
Description: Displays the line supply voltage at the input terminals of the line filter in alpha/beta components.
Index: [0] = Alpha component
[1] = Beta component
Note: The input terminals of the line filter form, for infeeds, the connection point of the Voltage Sensing Module (VSM) to
measure the line supply voltage.
For operation with VSM (p3400.5 = 1), the following applies:
The voltage measured values r3661 and r3662, transformed into the alpha/beta system are displayed in r3468.
For sensorless operation without VSM (p3400.5 = 0), the following applies:
The estimated values of the voltages from the line supply model of the PLL transformed into the alpha/beta system
are displayed in r3468.
Description: Calibration value for the RC filter of the zero crossover detection of the line supply voltage in the power unit.
For p3469 = 0, a new calibration is carried out at the next identification run with p3410 = 4 or p3410 = 5.
Note: The calibration value is saved in the EEPROM of the power unit (not on the CompactFlash card), as it involves a
characteristic/feature of the power unit.
Description: Displays the active current requirement due to the line filter.
Dependency: Refer to: r0038, p0221, p0222
p3463 Infeed, line angle change, phase failure detection / INF Phi phase fail
A_INF, S_INF Can be changed: T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-180.0 [°] 180.0 [°] 15.0 [°]
r3468[0...1] Infeed voltage alpha/beta line filter / INF V a/b filter
A_INF, S_INF Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
p3469[0...n] Latch delay time correction, zero crossover detection / t_latch corr PLL
A_INF, S_INF Can be changed: T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: PDS, p0120 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-10000.0 [µs] 10000.0 [µs] 0.0 [µs]
r3470 Infeed active current filter / INF I_act filter
A_INF Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]