List of parameters
Parameters
1-39
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
For p3900 not equal to 0, at the end of the quick commissioning, this parameter is automatically reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description: Sets the parameter filter to commission a drive.
Setting this parameter filters-out the parameters that can be written into in the various commissioning steps.
Values: 0: Ready
1: Quick commissioning
2: Power unit commissioning
3: Motor commissioning
4: Encoder commissioning
5: Technological application/units
15: Data sets
17: Basic positioning commissioning
25: Commissioning the position control
29: Download
30: Parameter reset
95: Safety Integrated commissioning
Note: The drive can only be powered-up outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
For p3900 not equal to 0, at the end of the quick commissioning, this parameter is automatically reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description: Sets the parameter filter for commissioning a terminal board 30 (TB30).
Setting this parameter filters-out the parameters that can be written into in the various commissioning steps.
For the BOP, this setting also causes the read access operations to be filtered.
Values: 0: Ready
29: Download
30: Parameter reset
Dependency: Refer to: p0970
Note: Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description: Sets the parameter filter for commissioning a Terminal Module 31 (TM31).
Setting this parameter filters-out the parameters that can be written into in the various commissioning steps.
p0010 Drive, commissioning parameter filter / Drv comm. par_filt
SERVO, VECTOR Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: 2800, 2846
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 95 1
p0010 TB30 commissioning parameter filter / TB30 comm.par_filt
TB30 Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 30 0
p0010 TM31 commissioning parameter filter / TM31 comm par_filt
TM31 Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 30 0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS S Series and is the answer not in the manual?

Siemens SINAMICS S Series Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS S Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals