Figure 2-233 8860 – Signals and monitoring functions, line supply voltage monitoring
- 8860 -
Function diagram
87654321
fp_8860_01_eng.vsd
DO: S_INF
SINAMICS S
04.07.07 V02.05.00
Smart Infeed - Signals and monitoring functions, line supply voltage monitoring
85 %
110 %
F06100 "Shutdown due to line supply undervoltage"
A06310 "Supply voltage (p0210) incorrectly parameterized"
p0283 (75 %)
p0282 (85 %)
p0281 (110 %)
A06105 "Line supply undervoltage"
A06301 "Line supply overvoltage"
Supply voltage
p0210
&
Nominal line
supply voltage
Calculated
actual line
supply voltage
[8850.4]
p0115[3] (2000.00 µs)
U_line supply calculated