Parameters
List of parameters
1-78
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
[2] = Power drawn
Dependency: Refer to: r0032
Note: The active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed (r0082[0]). The
unsmoothed, electric motor active power is displayed in r0082[2] without taking into account the motor losses.
Description: Displays the flux setpoint.
Description: Displays the flux actual value.
Description: Displays the flux actual value.
Index: [0] = Unsmoothed
[1] = Smoothed
Note: The flux actual value (index 1) smoothed with p1585 is only displayed for separately-excited synchronous motors.
In the following cases, the unsmoothed flux actual value is also displayed:
- in the range of the current model.
- during the pole position identification.
- for I/f control.
- for a stalled drive.
Description: Displays the actual active power factor.
r0083 CO: Flux setpoint / Flux setpoint
SERVO, VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 5722
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r0084 CO: Flux actual value / Flux act val
SERVO Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 5722
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r0084[0...1] CO: Flux actual value / Flux act val
VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 6726, 6730,
6731
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r0087 CO: Actual power factor / Cos phi act
VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 6730, 6731,
6799
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -