List of parameters
Parameters
1-271
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the send and receive telegram.
Values: 1: Standard telegram 1, PZD-2/2
2: Standard telegram 2, PZD-4/4
3: Standard telegram 3, PZD-5/9
4: Standard telegram 4, PZD-6/14
5: Standard telegram 5, PZD-9/9
6: Standard telegram 6, PZD-10/14
102: SIEMENS telegram 102, PZD-6/10
103: SIEMENS telegram 103, PZD-7/15
105: SIEMENS telegram 105, PZD-10/10
106: SIEMENS telegram 106, PZD-11/15
116: SIEMENS telegram 116, PZD-11/19
999: Free telegram configuration with BICO
Dependency: Refer to: p2038
Refer to: F01505, F01506
Note: For p0922 = 100 ... 199, p2038 is automatically set to 1 and p2038 can no longer be changed. This means that for
these telegrams, the "SIMODRIVE 611 universal" interface mode is set and cannot be changed.
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
Description: Sets the send and receive telegram.
Values: 999: Free telegram configuration with BICO
Dependency: Refer to: p2038
Refer to: F01505, F01506
Note: For p0922 = 100 ... 199, p2038 is automatically set to 1 and p2038 can no longer be changed. This means that for
these telegrams, the "SIMODRIVE 611 universal" interface mode is set and cannot be changed.
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
p0922 PROFIdrive telegram selection / PD Telegr_sel
SERVO Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2420,
2422, 2423, 2460, 2470
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1 999 999
p0922 PROFIdrive telegram selection / PD Telegr_sel
SERVO (Pos ctrl) Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2420,
2422, 2423, 2460, 2470
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
999 999 999