List of parameters
Parameters
1-513
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Depending on whether the speed controller optimization is carried out with or without encoder, different Kp/Tn
adaptations of the speed controller are set (p1464, p1465). If the drive should be controlled with as well as without
speed encoder, then we recommend the use of two drive data sets (p0180). These can then be executed with dif-
ferent speed controller adaptations.
Description: Sets the speed to determine the saturation characteristic and the encoder test.
The percentage value is referred to p0310 (rated motor frequency).
Dependency: Refer to: p0310, p1959
Refer to: F07983
Note: The saturation characteristics should be determined at an operating point with the lowest possible load.
Description: Displays the magnetizing currents of the identified saturation characteristic.
The values are referred to r0331.
Dependency: Refer to: p1959, p1960, r1963
Note: The saturation characteristic consists of the value pairs from p1962 and p1963 with the same index.
Description: Displays the magnetizing currents of the identified saturation characteristic.
The values are referred to r0331.
After they have been determined, the values are transferred to p0366 ... p0369.
Index: [0] = Value 1
[1] = Value 2
[2] = Value 3
[3] = Value 4
[4] = Value 5
Dependency: Refer to: r0331
p1961 Saturation characteristic speed to determine / Sat_char n determ
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
26 [%] 75 [%] 40 [%]
r1962[0...9] Saturation characteristic magnetizing current identified / Sat_char I_mag
SERVO Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r1962[0...4] Saturation characteristic, magnetizing current / Sat_char I_mag
VECTOR (n/M) Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]