Parameters
List of parameters
1-1042
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note: In order to permanently accept the acknowledgement of the fault that can be resolved, then it must be saved in a
non-volatile fashion (p0977).
Description: With p9905 = 1, the serial numbers and the hardware versions of all of the components are transferred from the
actual topology into the target topology and a new comparison is started..
For this device specialization, the components of the target topology may only differ from those of the actual topol-
ogy by the serial numbers.
With p9905 = 2, the serial numbers, the hardware versions and the order numbers of all of the components are
transferred from the actual topology into the target topology and a new comparison is started..
For this device specialization, the components of the target topology may only differ from those of the actual topol-
ogy by the serial numbers and order numbers.
Note: p9905 is automatically set to 0 at the end of the operation.
In order to permanently accept the data, it is necessary to save in a non-volatile fashion (p0977).
Description: Sets the type of comparison between the actual topology and target topology.
The comparison is started by setting the required value.
Values: 0: High: Compares the complete electronic rating plate
1: Average: Compares the component type and the Order number
2: Low: Compares the component type
3: Minimum: Compares the component class
99: Topology has different comparison stages
Note: The electronic rating plate comprises the following data:
- component type (e.g. "SMC20")
- Order No. (e.g. "6SL3055-0AA0-5BA0")
- manufacturer (e.g. SIEMENS)
- hardware version (e.g. "A")
- Serial No. (e.g. "T-P30050495")
When comparing the topology, the following data is compared in the target and actual topologies:
p9906 = 0: Component type, Order No., Hardware version, Manufacturer, Serial No.
p9906 = 1: Component type, Order No.
p9906 = 2: Component type
p9906 = 3: Component class (e.g. Sensor Module or Motor Module)
p9905 Device specialization / Device specializ.
CU_CX32, CU_S Can be changed: C1(1) Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Topology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 2 0
p9906 Topology comparison, comparison stage of all components / Topo_cmpr tot comp
CU_CX32, CU_S Can be changed: C1(1) Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Topology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 99 0