List of faults and alarms
Faults and Alarms
3-1729
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F35228 TM: Sampling time p4099[3] invalid
Drive object: TM41
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The value of the cycle time for the incremental encoder emulation, specified in p4099[3] does not correspond to a
valid value.
The system already changed the p4099[3] to a valid value.
The parameters of the TM41 involved must be saved on the CompactFlash card and a POWER ON carried out.
Remedy:
F35229 TM time slice de-activated
Drive object: TM41
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The required value of a cycle time in P4099 () is invalid.
The corresponding time slice was not activated.
Alarm value:
0 Digital input/outputs ( P4099(0) )
1 Analog input ( P4099 (1) )
3 Encoder emulation position setpoint ( P4099 (3) )
4 Encoder emulation speed setpoint ( P4099 (3) )
5 Encoder emulation speed setpoint ( P4099 (3) )
6 Internal sequencer of the TM41 (internal error)
Remedy: The sampling time P4099 (0) may not be zero. Change the sampling time corresponding to the error code.
F35230 HW problem with the TM module
Drive object: A_INF, B_INF, CU_LINK, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41, TM54F_MA,
TM54F_SL, VECTOR
Reaction: A_INFEED: OFF1 (NONE, OFF2)
SERVO: NONE
VECTOR: NONE
Acknowledge: POWER ON
Cause: The terminal module used has signaled an internal error. Signals of this module may not be evaluated and are poten-
tially incorrect.
Remedy: The module must be replaced if no other alarms that refer to a communications error are present in the system.
N35800 (F) TM: Group signal
Drive object: All objects
Reaction: A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
VECTOR: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
Acknowledge: NONE
Cause: The Terminal Module has detected at least one fault.
Remedy: Evaluates other actual messages.
Reaction upon F: A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
VECTOR: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
Acknowl. upon F: IMMEDIATELY
A35801 (F, N) TM DRIVE-CLiQ: Sign-of-life missing
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: A DRIVE-CLiQ communications error has occurred between the Control Unit and the Terminal Module involved.
Alarm value (r2124, interpret hexadecimal):
0A: The sign-of-life bit in the receive telegram is not set.