Parameters
List of parameters
1-114
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the maximum output current of the power unit.
Index: [0] = Catalog
[1] = Load duty cycle with high overload
[2] = Load duty cycle with low overload
[3] = S1 load duty cycle
[4] = S6 load duty cycle
Dependency: Refer to: p0205
Description: Sets the drive unit supply voltage (3-ph. AC).
The value corresponds to the rms value of the phase-to-phase rated line supply voltage.
Dependency: Refer to: p3400
Warning: If the infeed is continually in the controlled mode with high DC link voltages (p3510 > 660 V), depending on the par-
ticular application, this can damage the connected motors that have not been specified for these high voltages.
Before an active infeed with a line supply voltage p0210 > 415 V goes into pulsed operation it must be ensured that
all of the components connected to the DC link can be permanently operated with DC link voltages exceeding 660
V.
Controlled operation of booksize power units for p0210 > 415 V is possible if the maximum steady-state DC link
voltage (p0280) is increased as follows: p0280 >= 1.5 * p0210 and p0280 > 660 V.
In this case, the setpoint of the DC link voltage p3510 is not automatically adapted. We recommend p3510 = 1.5 *
p0210. Closed-loop voltage controlled operation is active with p3400.0 = 0 and p3400.3 = 1.
Notice: For p0210 > 415 V for booksize power units with a supply voltage of 3-ph. 380 ... 480 V, the smart mode is automat-
ically activated (p3400.0 = 1). In this case, the smart mode cannot be de-activated. This is because in the voltage
controlled mode, the maximum steady-state DC link voltage (p0280) would be exceeded.
For booksize power units with supply voltage of 3-ph. 380 ... 480 V AC, the following applies:
380 V <= p0210 <= 400 V --> Pre-assignment, setpoint for the DC link voltage: p3510 = 600 V
401 V <= p0210 <= 415 V --> Pre-assignment, setpoint for the DC link voltage: p3510 = 625 V
416 V <= p0210 <= 480 V --> Smart Mode with non-regulated DC link voltage: p3510 = 1.35 * p0210
Note: When pre-assigning the setpoint for the DC link voltage (p3510), the following is generally valid:
p3510 = 1.5 * p0210
The voltage range for the supply voltage depends on the type and the voltage class of the power unit.
Active Line Module, 400 V unit: 380 V <= p0210 <= 480 V
Active Line Module, 690 V unit: 660 V <= p0210 <= 690 V
Active Line Module, 500/690 V unit: 500 V <= p0210 <= 690 V
Smart Line Module, 400 V unit: 380 V <= p0210 <= 480 V
Smart Line Module, 690 V unit: 500 V <= p0210 <= 690 V
r0209[0...4] Power unit, maximum current / PU I_max
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 8750, 8850,
8950
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p0210 Drive unit line supply voltage / Supply voltage
A_INF, S_INF Can be changed: C2(1) Calculated: - Access level: 1
Data type: Floating Point Dynamic index: - Func. diagram: 8750, 8960
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
100 [Vrms] 1000 [Vrms] 400 [Vrms]