Siemens SINAMICS S Series - p3761[0...n] APC load velocity controller 1 rate time; APC v_load ctr1 Tv; p3765[0...n] APC load speed controller 2 P gain; APC n_load ctr2 Kp; p3765[0...n] APC load velocity controller 2 P gain; APC v_load ctr2 Kp; p3766[0...n] APC load speed controller 2 rate time; APC n_load ctr2 Tv

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-740
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the rate time of the load velocity controller 1 for APC (Advanced Positioning Control).
The rate time acts on the load acceleration in the branch for filter 2.1 and 2.2.
Description: Sets the proportional gain of the load speed controller 2 for APC (Advanced Positioning Control).
The gain acts on the difference between the speed setpoint and load speed in the branch for filter 3.1 and 3.2.
Description: Sets the proportional gain of the load velocity controller 2 for APC (Advanced Positioning Control).
The gain acts on the difference between the velocity setpoint and load velocity in the branch for filter 3.1 and 3.2.
Description: Sets the rate time of the load speed controller 2 for APC (Advanced Positioning Control).
The rate time acts on the load acceleration in the branch for filter 3.1 and 3.2.
Description: Sets the rate time of the load velocity controller 2 for APC (Advanced Positioning Control).
The rate time acts on the load acceleration in the branch for filter 3.1 and 3.2.
p3761[0...n] APC load velocity controller 1 rate time / APC v_load ctr1 Tv
SERVO (APC, Lin) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 7012
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
-500.00 [ms] 500.00 [ms] 0.00 [ms]
p3765[0...n] APC load speed controller 2 P gain / APC n_load ctr2 Kp
SERVO (APC) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 7012
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
-100.000 100.000 0.000
p3765[0...n] APC load velocity controller 2 P gain / APC v_load ctr2 Kp
SERVO (APC, Lin) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 7012
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
-100.000 100.000 0.000
p3766[0...n] APC load speed controller 2 rate time / APC n_load ctr2 Tv
SERVO (APC) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 7012
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
-500.00 [ms] 500.00 [ms] 0.00 [ms]
p3766[0...n] APC load velocity controller 2 rate time / APC v_load ctr2 Tv
SERVO (APC, Lin) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 7012
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
-500.00 [ms] 500.00 [ms] 0.00 [ms]