Active Infeed
Function Diagrams
2-1363
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-235 8920 – Control word sequence control infeed
- 8920 -
Function diagram
87654321
fp_8920_01_eng.vsd
DO: A_INF
SINAMICS S
07.07.06 V02.05.00
Active Infeed - Control word, sequence control infeed
p0844[C] (1)
1 OFF2 (electrical)
p0845[C] (1)
2 OFF2 (electrical)
11
12
13
14
15
p0840[C] (0)
p0852[C] (1)
9
10
8
7
6
5
4
3
2
1
0
Bit No.
<2>
<2> PROFIdrive interconnection: For the manufacturer-specific
PROFIdrive telegram, the upper input is connected to
PROFIdrive signal A_STW1 [2447]. This only involves CDS0.
To the control unit [8932]r0898.0
To the control unit [8932]r0898.1
To the control unit [8932]r0898.3
r0898.10
r0898.5
r0898.6
p0854[C] (0)
p3532[C] (0)
p3533[C] (0)
r0898
STW seq_ctrl INF
= ON (close pre-charging/line contactor, pulses can be enabled)
0 = OFF1 (reduce Vdc along a ramp, pulse cancellation and open pre-charging/line contactor)
Control word sequence control infeed
1 = Operating condition no OFF2 (enable is possible)
0 = OFF2 (immediate pulse cancellation, open pre-charging/line contactor and power-on inhibit)
Reserved
1 = Enable operation (pulses can be enabled)
0 = Inhibit operation (cancel pulses)
Reserved
Reserved
Reserved
Reserved
Reserved
1 = Control via PLC
1 = Inhibit regenerative operation
Reserved
1 = Inhibit motoring operation
Reserved
Reserved
<1>
Reserved
<3> Is predefined via the PC if the master control is retrieved.
<3>
<3>
<3>
<3>
<1> To ensure that the drive objects accepts the process data
(PZD), bit 10 must be set in the first PZD word.
p0115[3] (2000.00 µs)