Siemens SINAMICS S Series - p1804[0...n] Filter time constant smoothed modulation index; T_filt mod_idxSmth; p1806[0...n] Filter time constant Vdc correction; T_filt Vdc_corr; r1807 Actual DC-link voltage to calculate the modulation depth; VdcActValMod_depth; r1808 DC link voltage actual value for V_max calculation; Vdc act val V_max

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-487
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Filter time constant for the smoothed modulation index to change over the modulator mode.
Description: Sets the filter time constant of the DC link voltage used to calculate the modulation depth.
Description: DC link voltage that is used to convert the setpoint voltage into an equivalent modulation depth.
Note: p1737 can be used for filtering.
Description: DC link voltage used to determine the maximum possible output voltage.
Description: Displays the effective modulator mode.
p1804[0...n] Filter time constant smoothed modulation index / T_filt mod_idxSmth
VECTOR Can be changed: U, T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 10.0 [ms]
p1806[0...n] Filter time constant Vdc correction / T_filt Vdc_corr
VECTOR Can be changed: U, T Calculated: CALC_MOD_REG Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 0.0 [ms]
r1807 Actual DC-link voltage to calculate the modulation depth / VdcActValMod_depth
VECTOR Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: 5_2 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r1808 DC link voltage actual value for V_max calculation / Vdc act val V_max
VECTOR Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: 5_2 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r1809 Modulator mode actual / Modulator mode act
VECTOR Can be changed: - Calculated: - Access level: 4
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1 8 -