Siemens SINAMICS S Series - p1248[0...n] DC link voltage threshold lower; Vdc lower thresh; p1249[0...n] Vdc_max controller speed threshold; Vdc_max n_thresh; p1250[0...n] Vdc controller proportional gain; Vdc_ctrl Kp

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-357
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the lower threshold for the DC link voltage.
For p1240 = 2, 3, 8, 9, this threshold is used as limit setpoint for the Vdc_min controller.
For p1240 = 5, 6, for DC link voltages below this threshold, an appropriate fault is output.
Dependency: Refer to: p1240, p1244, p1250
Note: For p1248 > 0.93 * "parameterized DC link voltage" input of values is rejected. For p0204.0 = 1, the following
applies:
"Parameterized DC link voltage" = p0210
For p0204.0 = 0, the following applies:
"Parameterized DC link voltage" = p0210 * 1.4142
Description: Sets the lower speed threshold for the Vdc_max controller. When this speed threshold is fallen below, the Vdc_max
control is switched-out and the speed is controlled using the ramp-function generator.
Note: For fast braking where the ramp-function generator tracking was active, it is possible to prevent the drive rotating in
the opposite direction by increasing the speed threshold and setting a final rounding-off time in the ramp-function
generator (p1131). This is supported using a dynamic setting of the speed controller.
Description: Sets the proportional gain for the Vdc controller (DC link voltage controller).
Dependency: Refer to: p1240, p1244, p1248
Description: Sets the proportional gain for the Vdc controller (DC link voltage controller).
Dependency: The effective proportional gain is obtained taking into account p1243 (Vdc_max controller dynamic factor).
p1248[0...n] DC link voltage threshold lower / Vdc lower thresh
SERVO Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5650
P-Group: Functions Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
100 [V] 1000 [V] 450 [V]
p1249[0...n] Vdc_max controller speed threshold / Vdc_max n_thresh
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Functions Units group: 3_1 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.0 [RPM] 210000.0 [RPM] 10.0 [RPM]
p1250[0...n] Vdc controller proportional gain / Vdc_ctrl Kp
SERVO Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5650
P-Group: Functions Units group: 19_1 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.00 [A/V] 10.00 [A/V] 1.00 [A/V]
p1250[0...n] Vdc controller proportional gain / Vdc_ctrl Kp
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.00 100.00 1.00