Description: Sets the lower threshold for the DC link voltage.
For p1240 = 2, 3, 8, 9, this threshold is used as limit setpoint for the Vdc_min controller.
For p1240 = 5, 6, for DC link voltages below this threshold, an appropriate fault is output.
Dependency: Refer to: p1240, p1244, p1250
Note: For p1248 > 0.93 * "parameterized DC link voltage" input of values is rejected. For p0204.0 = 1, the following
applies:
"Parameterized DC link voltage" = p0210
For p0204.0 = 0, the following applies:
"Parameterized DC link voltage" = p0210 * 1.4142
Description: Sets the lower speed threshold for the Vdc_max controller. When this speed threshold is fallen below, the Vdc_max
control is switched-out and the speed is controlled using the ramp-function generator.
Note: For fast braking where the ramp-function generator tracking was active, it is possible to prevent the drive rotating in
the opposite direction by increasing the speed threshold and setting a final rounding-off time in the ramp-function
generator (p1131). This is supported using a dynamic setting of the speed controller.
Description: Sets the proportional gain for the Vdc controller (DC link voltage controller).
Dependency: Refer to: p1240, p1244, p1248
Description: Sets the proportional gain for the Vdc controller (DC link voltage controller).
Dependency: The effective proportional gain is obtained taking into account p1243 (Vdc_max controller dynamic factor).
p1248[0...n] DC link voltage threshold lower / Vdc lower thresh
SERVO Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5650
P-Group: Functions Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
100 [V] 1000 [V] 450 [V]
p1249[0...n] Vdc_max controller speed threshold / Vdc_max n_thresh
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Functions Units group: 3_1 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.0 [RPM] 210000.0 [RPM] 10.0 [RPM]
p1250[0...n] Vdc controller proportional gain / Vdc_ctrl Kp
SERVO Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5650
P-Group: Functions Units group: 19_1 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.00 [A/V] 10.00 [A/V] 1.00 [A/V]
p1250[0...n] Vdc controller proportional gain / Vdc_ctrl Kp
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.00 100.00 1.00