Siemens SINAMICS S Series - p4068[0...1] TB30 analog inputs, window to suppress noise; TB30 AI window; p4068[0...1] TM31 analog inputs, window to suppress noise; TM31 AI window; p4068[0...0] TM41 analog input, window to suppress noise; TM41 AI window; p4069[0...1] BI: TB30 analog inputs, signal source for enable; TB30 AI enable

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-804
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the noise suppression window for the analog inputs of Terminal Board 30 (TB30).
Changes less than the window are suppressed.
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Description: Sets the window for noise suppression for the analog inputs of terminal module 31 (TM31).
Changes less than the window are suppressed.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Sets the noise suppression window for the analog input of terminal module 41 (TM41).
Changes less than the window are suppressed.
Index: [0] = AI 0 (X523.1/X523.2)
Description: Sets the signal source for enabling the analog inputs of the Terminal Board 30 (TB30).
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
p4068[0...1] TB30 analog inputs, window to suppress noise / TB30 AI window
TB30 Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 20.00 [%] 0.00 [%]
p4068[0...1] TM31 analog inputs, window to suppress noise / TM31 AI window
TM31 Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 20.00 [%] 0.00 [%]
p4068[0...0] TM41 analog input, window to suppress noise / TM41 AI window
TM41 Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9663
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 20.00 [%] 0.00 [%]
p4069[0...1] BI: TB30 analog inputs, signal source for enable / TB30 AI enable
TB30 Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1