Parameters
List of parameters
1-804
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the noise suppression window for the analog inputs of Terminal Board 30 (TB30).
Changes less than the window are suppressed.
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Description: Sets the window for noise suppression for the analog inputs of terminal module 31 (TM31).
Changes less than the window are suppressed.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Sets the noise suppression window for the analog input of terminal module 41 (TM41).
Changes less than the window are suppressed.
Index: [0] = AI 0 (X523.1/X523.2)
Description: Sets the signal source for enabling the analog inputs of the Terminal Board 30 (TB30).
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
p4068[0...1] TB30 analog inputs, window to suppress noise / TB30 AI window
TB30 Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 20.00 [%] 0.00 [%]
p4068[0...1] TM31 analog inputs, window to suppress noise / TM31 AI window
TM31 Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 20.00 [%] 0.00 [%]
p4068[0...0] TM41 analog input, window to suppress noise / TM41 AI window
TM41 Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9663
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 20.00 [%] 0.00 [%]
p4069[0...1] BI: TB30 analog inputs, signal source for enable / TB30 AI enable
TB30 Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1