List of faults and alarms
Faults and Alarms
3-1549
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A07466 EPOS: Traversing block number assigned a multiple number of times
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The same traversing block number was assigned a multiple number of times.
Alarm value (r2124, interpret decimal):
Number of the traversing block that was assigned a multiple number of times.
Remedy: Correct the traversing blocks.
A07467 EPOS: Traversing block has illegal task parameters
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The task parameter in the traversing block contains an illegal value.
Alarm value (r2124, interpret decimal):
Number of the traversing block with an illegal task parameter.
Remedy: Correct the task parameter in the traversing block.
A07468 EPOS: Traversing block jump destination does not exist
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: In a traversing block, a jump was programmed to a non-existent block.
Alarm value (r2124, interpret decimal):
Number of the traversing block with a jump destination that does not exist.
Remedy: - correct the traversing block.
- add the missing traversing block.
A07469 EPOS: Traversing block < target position < software limit switch minus
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: In the traversing block the specified absolute target position lies outside the range limited by the software limit switch
minus.
Alarm value (r2124, interpret decimal):
Number of the traversing block with illegal target position.
Remedy: - correct the traversing block.
- change software limit switch minus (CI: p2578, p2580).
A07470 EPOS: Traversing block> target position > software limit switch plus
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: In the traversing block the specified absolute target position lies outside the range limited by the software limit switch
plus.
Alarm value (r2124, interpret decimal):
Number of the traversing block with illegal target position.
Remedy: - correct the traversing block.
- change software limit switch plus (CI: p2579, p2581).