Description: Sets the normalized proportional gain for the circulating current controller.
Note: A value of 100 % corresponds to the basic setting derived from loop control parameters (p3421, p3622).
Description: Sets the proportional gain for the circulating current controller.
The parameter is pre-set to the cable resistance.
Description: Sets the normalized integral time of the circulating current controller.
Note: A value of 100 % corresponds to the basic setting derived from the controller sampling time p0115[0].
The integral component of the controller is de-activated with p7037 = 0.
Description: Sets the integral time of the circulating current controller.
The parameter is referred to the current controller sampling time (p0115[0]).
Dependency: Refer to: p0115
p7036 Infeed par_cct circulating current controller proportional gain / Circ_I Kp
A_INF (Parallel),
S_INF (Parallel)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00000 [%] 1000.00000 [%] 100.00000 [%]
p7036[0...n] Par_circuit circulating current control proportional gain / Circ_I Kp
VECTOR (Parallel) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00000 [Ohm] 20.00000 [Ohm] 0.00000 [Ohm]
p7037 Infeed par_cct circulating current control integral time / I_circ Tn
A_INF (Parallel),
S_INF (Parallel)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [%] 100000.0 [%] 100.0 [%]
p7037[0...n] Par_circuit circulating current control integral time / I_circ Tn
VECTOR (Parallel) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Modulation Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
2.0 1000.0 4.0