List of parameters
Parameters
1-53
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the actual temperature in the motor.
Note: For r0035 not equal to -200.0 °C, the following applies:
- this temperature display is valid.
- a KTY sensor is connected.
- for induction motors, the thermal motor model is activated (p0600 = 0 or p0601 = 0).
For r0035 equal to -200.0 °C, the following applies:
- this temperature display is not valid (temperature sensor error).
- a PTC sensor is connected.
- for synchronous motors, the thermal motor model is activated (p0600 = 0 or p0601 = 0).
Description: Displays the temperature currently measured at X21 (booksize) or X41 (chassis).
For a BLM with internal Braking Module, a bemetallic sensor must be connected-up to monitor the temperature of
the braking resistor. The temperature sensor type is indicated using p0601 and cannot be changed for the existing
internal Braking Module.
Temperature within permissible limit values: r0035 = -50°C
Temperature outside the permissible limit values: r0035 = -250°C
Dependency: Refer to: F06907, F06908
Notice: The function in r0192.11 must be available in order to obtain a correct display.
Note: For r0035 equal to -200.0 °C, the following applies:
- "no sensor available" selected in p0601!
For r0035 equal to -300.0 °C, the following applies:
- a KTY84 is selected in p0601 but is not connected!
- the temperature display is not valid (temperature sensor error)!
Description: Displays the power unit overload determined using the I2t calculation.
A current reference value is defined for the I2t monitoring of the power unit. It represents the current that can be
conducted by the power unit without any influence of the switching losses (e.g. the continuously permissible current
of the capacitors, inductances, busbars, etc.).
If the I2t reference current of the power unit is not exceeded, then an overload (0 %) is not displayed.
In the other case, the degree of thermal overload is calculated, whereby 100% results in a trip.
r0035 CO: Motor temperature / Motor temperature
SERVO, VECTOR Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 8016
P-Group: Displays, signals Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]
r0035 CO: Temperature input / Temp input
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]
r0036 Power unit overload I2t / PU overload I2t
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8014
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]