Parameters
List of parameters
1-30
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
1.2 List of parameters
Product: SINAMICS S, Version: 2503100, Language: eng
Description: Operating display for the Control Unit (CU).
Values: 0: [00] Operation
10: [10] Ready
20: [20] Wait for run-up
31: [31] Commissioning software download active
33: [33] Remove topology error / acknowledge
34: [34] Exit the commissioning mode
35: [35] Carry out first commissioning
70: [70] Initialization
80: [80] Reset active
99: [99] Internal software error
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
Description: Operating display for the infeed.
Values: 0: [00] Operation - everything enabled
21: [21] Ready - set "enable operation" = "1" (p0852)
31: [31] Rdy to power-up - pre-chrg running (p0857)
32: [32] Ready to power-up - set "ON/OFF1" = "0/1" (p0840)
41: [41] Power-on inhibit - set "ON/OFF1" = "0" (p0840)
42: [42] Power-on inhibit - set "OC/OFF2" = "1" (p0844, p0845)
44: [44] Power-on inhibit - connect 24 V to terminal EP (hardware)
45: [45] Power-on inhib - remove fault cause, acknowledge fault
46: [46] Power-on inhibit - exit comm mode (p0009, p0010)
60: [60] Infeed de-activated/not operational
250: [250] Device signals a topology error
Dependency: Refer to: r0046
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
Note: OC: Operating condition
EP: Enable Pulses (pulse enable)
COMM: Commissioning
r0002 Control Unit operating display / CU op_display
CU_CX32, CU_S Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 99 -
r0002 Infeed operating display / INF op_display
A_INF, S_INF Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 250 -