Parameters
List of parameters
1-118
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the inductance between the filter and power unit.
Note: The parameter is automatically pre-assigned depending on the power unit being used and matches the specified
Siemens commutating reactors.
For a parallel circuit, the value corresponds to the inductance of a power unit.
Description: Sets the resistance between the filter and power unit
Note: The parameter is automatically pre-assigned depending on the power unit being used and matches the specified
Siemens commutating reactors.
For a parallel circuit, the value corresponds to the resistance of a power unit.
Description: Sets the inductance between line supply and filter.
Note: The value must be, for example, appropriately increased if an additional inductance (reactor or transformer is
installed in front of the filter).
Description: Sets the resistance between the line supply and filter.
Note: The value must be, for example, appropriately increased if an additional resistor is installed in front of the filter.
p0223 Infeed inductance between filter and power unit / INF L filter/PU
A_INF, S_INF Can be changed: C2(1) Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8850, 8950
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.001 [mH] 1000.000 [mH] 2.100 [mH]
p0224 Infeed resistance between filter and power unit / INF R filter/PU
A_INF, S_INF Can be changed: C2(1) Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8850, 8950
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00000 [Ohm] 100.00000 [Ohm] 0.00100 [Ohm]
p0225 Infeed inductance between line supply and filter / INF L line/filter
A_INF, S_INF Can be changed: C2(1) Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8850, 8950
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.001 [mH] 1000.000 [mH] 0.001 [mH]
p0226 Infeed resistance between line supply and filter / INF R line/filter
A_INF, S_INF Can be changed: C2(1) Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8850, 8950
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [Ohm] 100.00 [Ohm] 0.00 [Ohm]