List of faults and alarms
Faults and Alarms
3-1453
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Remedy: - remove the corresponding component.
- change the setting "de-activat and not present".
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. set-
point/actual value comparison).
See also: p0105 (Activate/de-activate drive object), p0125 (Activate/de-activate power unit components), p0145
(Voltage Sensing Module, activate/de-activate), p0155 (Voltage Sensing Module, activate/de-activate)
A01315 Drive object not ready for operation
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: For the active drive object involved, at least one activated component is missing.
Note:
All other active and operational drive objects can be in the "RUN" state.
Remedy: The alarm automatically disappears again with the following actions:
- de-activate the drive object involved (p0105 = 0).
- de-activate the components involved (p0125 = 0, p0145 = 0, p0155 = 0, p0165 = 0).
- re-insert the components involved.
See also: p0105 (Activate/de-activate drive object), p0125 (Activate/de-activate power unit components), p0145
(Voltage Sensing Module, activate/de-activate), p0155 (Voltage Sensing Module, activate/de-activate)
A01316 Drive object inactive and again ready for operation
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: If, when inserting a component of the target topology, an inactive, non-operational drive object becomes operational
again. The associated parameter of the component is, in this case, set to "activate" (p0125, p0145, p0155, p0165).
Note:
This is the only message, that is displayed for a de-activated drive object.
Remedy: The alarm automatically disappears again with the following actions:
- activate the drive object involved (p0105 = 1).
- again withdraw the components involved.
See also: p0105 (Activate/de-activate drive object)
A01317 De-activated component again present
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: If a component of the target topology for an active drive object is inserted and the associated parameter of the com-
ponent is set to "de-activate" (p0125, p0145, p0155, p0165).
Note:
This is the only message, that is displayed for a de-activated component.
Remedy: The alarm automatically disappears again with the following actions:
- activate the components involved (p0125 = 1, p0145 = 1, p0155 = 1, p0165 = 1).
- again withdraw the components involved.
See also: p0125 (Activate/de-activate power unit components), p0145 (Voltage Sensing Module, activate/de-acti-
vate), p0155 (Voltage Sensing Module, activate/de-activate)
A01318 BICO: De-activated interconnections present
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: This alarm is output:
If an inactive/non-operational drive object is again active/ready for operation
and
r9498[] or r9499[] are not empty
and
the connections listed in r9498[] and r9499 have actually been changed