List of parameters
Parameters
1-35
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the access level for reading and writing parameters using the Basic Operator Panel (BOP) and Advanced
Operator Panel (AOP).
Values: 0: User-defined
1: Standard
2: Extended
3: Expert
4: Service
Note: Access level 0 (user-defined):
Parameters from the user-defined list (p0013).
Access level 1 (standard):
Parameters for the simplest operator control possibility (e.g. p1120 = ramp-function generator, ramp-up time).
Access level 2 (extended):
Parameters to operate the basic functions of the drive unit.
Access level 3 (experts):
Expert know-how is required for these parameters (e.g. BICO parameterization).
Access level 4 (service):
For these parameters, it is necessary that authorized service personnel enter the appropriate password (p3950).
Description: Sets the display filter for parameters for Basic Operator Panel (BOP) and Advanced Operator Panel (AOP).
Values: 0: All parameters
1: Displays, signals
2: Power unit
3: Motor
4: Encoder/pos enc
5: Technology/units
7: Digital inputs/outputs commands sequence control
8: Analog inputs/outputs
10: Setpoint channel/ramp-fct generator
12: Functions
13: V/f control
14: Control
15: Data sets
17: Basic positioner
18: Gating unit
19: Motor identification
20: Communication
21: Faults, alarms, monitoring functions
25: Closed-loop position control
28: Free function blocks
47: Trace and function generator
50: OA parameter
90: Topology
p0003 BOP access level / BOP access level
CU_CX32, CU_S Can be changed: C1, U, T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 4 1
p0004 BOP display filter / BOP display filter
CU_CX32, CU_S Can be changed: C2(1), U, T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: ASM Expert list: 1
Min Max Factory setting
0 99 0