List of faults and alarms
Faults and Alarms
3-1681
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F32837 (N, A) Encoder 2 DRIVE-CLiQ: Component fault
Drive object: All objects
Reaction: A_INFEED: OFF2
SERVO: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
VECTOR: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: Fault detected on the DRIVE-CLiQ component involved. Faulty hardware cannot be excluded.
Fault value (r0949, interpret hexadecimal):
20: Error in the telegram header.
23: Receive error: The telegram buffer memory contains an error.
42: Send error: The telegram buffer memory contains an error.
43: Send error: The telegram buffer memory contains an error.
Remedy: - check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F32845 (N, A) Encoder 2 DRIVE-CLiQ: Cyclic data transfer error
Drive object: All objects
Reaction: A_INFEED: OFF2
SERVO: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
VECTOR: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: DRIVE-CLiQ communications error between the Control Unit and the encoder involved.
Fault value (r0949, interpret hexadecimal):
0B: Synchronization error during alternating cyclic data transfer.
Remedy: Carry out a POWER ON.
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F32850 (N, A) Encoder 2: Sensor Module, internal software error
Drive object: All objects
Reaction: A_INFEED: OFF2 (NONE)
SERVO: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
VECTOR: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
Acknowledge: POWER ON
Cause: Internal software error in the Sensor Module of encoder 2.
Fault value (r0949, interpret decimal):
1: Background time slice is blocked.
2: Checksum over the code memory is not OK.
10000: OEM memory of the EnDat encoder contains data that cannot be interpreted.
Remedy: - replace the Sensor Module.
- if required, upgrade the firmware in the Sensor Module.
- contact the Hotline.