Parameters
List of parameters
1-170
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
2112: 40000 nm, 1 Vpp, A/B R distance-coded
2151: 16000 nm, 1 Vpp, A/B, EnDat, resolution 100 nm
3001: 1024 HTL A/B R
3002: 1024 TTL A/B R
3003: 2048 HTL A/B R
3005: 1024 HTL A/B
3006: 1024 TTL A/B
3007: 2048 HTL A/B
3008: 2048 TTL A/B
3009: 1024 HTL A/B unipolar
3011: 2048 HTL A/B unipolar
3020: 2048 TTL A/B R, with sense
3081: SSI, Singleturn, 24 V
3082: SSI, Multiturn 4096, 24 V
3090: 4096, HTL, A/B, SSI, Singleturn
9999: User-defined
10000: Identify encoder
10050: Encoder with EnDat interface identified
Caution: An encoder type with p0400 < 9999 defines an encoder for which there is an encoder parameter list. When select-
ing a catalog encoder (p0400 < 9999) the parameters from the encoder parameter list cannot be changed (write
protection). To remove write protection, the encoder type should be set to an unlisted encoder (p0400 = 9999).
Notice: The list for motor codes /encoder codes can be found in the following literature:
SINAMICS S List Manual
Note: The connected encoder can be identified by p0400 = 10000. This means that the encoder must support this and is
possible in the following cases: Motor with DRIVE-CLiQ, encoder with EnDat interface.
If an identification is not possible, then p0400 is set to 0.
The encoder data (e.g. pulse number p0408) can only be changed when p0400 = 9999.
When using an encoder with track A/B and zero pulse, as standard, fine synchronization is not set using the zero
mark. If, for a synchronous motor, the fine synchronization is to be realized using a zero mark, then the following
must be executed:
- set p0400 to 9999
- set p0404.15 to 1
Prerequisite:
Coarse synchronization must be selected (e.g. pole position identification) and the zero pulse of the encoder must
either be mechanically or electronically (p0431) adjusted to the pole position.
Description: Selects the encoder from the list of encoder types that the OEM supports.
Note: The connected encoder can be identified by p0400 = 10000. This means that the encoder must support this and is
possible in the following cases: Motor with DRIVE-CLiQ, encoder with EnDat interface.
If an identification is not possible, then p0400 is set to 0.
The encoder data (e.g. pulse number p0408) can only be changed when p0400 = 9999.
Using p0400 = 20000, the encoder type can be selected from the list of OEM encoders using p0401.
p0401[0...n] Encoder type, OEM selection / Enc type OEM sel
SERVO, VECTOR Can be changed: C2(1, 4) Calculated: - Access level: 2
Data type: Integer16 Dynamic index: EDS, p0140 Func. diagram: 1580, 4704
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 32767 0