Parameters
List of parameters
1-210
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the power unit number to which the temperature sensor is connected. The value corresponds to the Power unit
Data Set number (PDS) of the power unit. The number of power unit data sets is defined in p0120.
Description: Sets the signal source to evaluate the motor temperature via a BICO interconnection.
Dependency: Refer to: p0600
Note: Temperature sensor KTY: Valid temperature range -48 °C ... 248 °C.
PTC temperature sensor:
For the -50 °C, the following applies: Motor temperature < nominal response temperature of the PTC.
For the 250 °C, the following applies: Motor temperature >= nominal response temperature of the PTC.
Note:
When using a Terminal Module 31 (TM31), the following applies:
- the sensor type used is set using p4100.
- the temperature signal is interconnected using CO: r4105.
Description: Sets the alarm threshold for monitoring the motor temperature.
Dependency: Refer to: p0606
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Description: Sets the alarm threshold for monitoring the motor temperature.
Dependency: Refer to: p0606
p0602 Par_circuit power unit number, temperature sensor / PU_No temp_sensor
VECTOR (Parallel) Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 10 0
p0603 CI: Motor temperature signal source / Mot temp S_src
SERVO, VECTOR Can be changed: C2(3), T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dynamic index: - Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p0604[0...n] Motor overtemperature alarm threshold / Mot TempAlrmThresh
SERVO Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [°C] 200.0 [°C] 120.0 [°C]
p0604[0...n] Motor overtemperature alarm threshold / Mot TempAlrmThresh
VECTOR Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [°C] 200.0 [°C] 130.0 [°C]