List of parameters
Parameters
1-159
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the rotor/secondary section leakage inductance of the motor.
For separately-excited synchronous motors: Sets the damping inductance in the rotor direction (d-axis).
This value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identification routine
(p1910) (not for separately-excited synchronous motors).
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
The parameter is automatically preset for motors from the motor list (p0301).
VECTOR:
If the stator leakage inductance (p0358) for induction motors is changed outside the commissioning phase (p0010 >
0), then the magnetizing inductance (p0360) is automatically adapted to the new EMF (r0337). After this, we recom-
mend that the saturation characteristic measurement is repeated (p1960).
Description: Sets the damping inductance of the separately-excited synchronous motor quadrature to the rotor direction (q axis).
This parameter value is automatically calculated using the motor model (p0340 = 1, 2).
Description: Sets the magnetizing inductance of the motor.
For separately-excited synchronous motors: Sets the saturated magnetizing inductance in the rotor direction (d-
axis).
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica-
tion routine (p1910) (not for separately-excited synchronous motors).
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
The parameter is automatically preset for motors from the motor list (p0301).
p0358[0...n] Motor rotor leakage inductance / damping inductance, d axis / Mot L_r leak / LDd
SERVO, VECTOR Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 15_1 Unit selection: p0349
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
0.00000 [mH] 1000.00000 [mH] 0.00000 [mH]
p0359[0...n] Motor damping inductance, q axis / Mot L_damp q
VECTOR Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 15_1 Unit selection: p0349
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
0.00000 [mH] 1000.00000 [mH] 0.00000 [mH]
p0360[0...n] Motor magnetizing inductance/magn. inductance, d axis saturated / Mot Lh/Lh d sat
SERVO, VECTOR Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 15_1 Unit selection: p0349
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
0.00000 [mH] 10000.00000 [mH] 0.00000 [mH]