Parameters
List of parameters
1-356
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the switch-in level for the Vdc-min controller (kinetic buffering).
The value is obtained as follows:
AC/AC device: p1245[V] = p1245[%] * sqrt(2) * p0210
DC/AC device: p1245[V] = p1245[%] * p0210
Dependency: Refer to: p0210
Warning: An excessively large value may adversely influence normal drive operation. The values up to 150 % are intended
for operating modes p1240 = 5, 6.
Note: For SINAMICS GM/SM, the following applies:
Minimum value = 0.75, Maximum value = 0.90
Description: Displays the switch-in level for the Vdc_min controller (kinetic buffering).
Description: Sets the dynamic factor for the Vdc-min controller (kinetic buffering).
100 % means that p1250, p1251 and p1252 (gain, integral time and rate time) are used corresponding to their basic
settings and based on a theoretical controller optimization.
If subsequent optimization is required, then this can be realized using the dynamic factor. In this case p1250,
p1251, p1252 are weighted with the dynamic factor p1247.
If several modules are connected to the DC link, then the dynamic factor must be increased corresponding to the
ratio of the additional capacitances to the capacitance of the module involved.
Note: The pre-setting of the dynamic factor is based on the power units connected at DRIVE-CLiQ. It is assumed that the
power unit, connected via DRIVE-CLiQ is also electrically connected to the DC link. If this is not the case, then the
dynamic factor must be optimized manually.
p1245[0...n] Vdc_min controller switch-in level (kinetic buffering) / Vdc_min on_level
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
65 [%] 150 [%] 76 [%]
r1246 Vdc_min controller switch-in level (kinetic buffering) / Vdc_min on_level
VECTOR (n/M) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 6220
P-Group: Functions Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
p1247[0...n] Vdc_min controller dynamic factor (kinetic buffering) / Vdc_min dyn_factor
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6220
P-Group: Functions Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
1 [%] 10000 [%] 100 [%]