Siemens SINAMICS S Series - p2207[0...n] CO: Technology controller, fixed value 7; Tec_ctrl fix val 7; p2208[0...n] CO: Technology controller, fixed value 8; Tec_ctrl fix val 8; p2209[0...n] CO: Technology controller, fixed value 9; Tec_ctrl fix val 9; p2210[0...n] CO: Technology controller, fixed value 10; Tec_ctrl fix val10

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-607
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the value for fixed value 7 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive objects always acts on the effective data set.
Description: Sets the value for fixed value 8 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive objects always acts on the effective data set.
Description: Sets the value for fixed value 9 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive objects always acts on the effective data set.
Description: Sets the value for fixed value 10 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive objects always acts on the effective data set.
p2207[0...n] CO: Technology controller, fixed value 7 / Tec_ctrl fix val 7
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 7950
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 70.00 [%]
p2208[0...n] CO: Technology controller, fixed value 8 / Tec_ctrl fix val 8
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 7950
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 80.00 [%]
p2209[0...n] CO: Technology controller, fixed value 9 / Tec_ctrl fix val 9
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 7950
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 90.00 [%]
p2210[0...n] CO: Technology controller, fixed value 10 / Tec_ctrl fix val10
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 7950
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]