Parameters
List of parameters
1-228
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the bidirectional digital inputs/outputs as an input or output.
Notice: To the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note: DI/DO: Bidirectional Digital Input/Output
Description: Sets the bidirectional digital inputs/outputs as an input or output.
Description: Sets the signal source for terminal DI/DO 8 (X122.7).
Notice: To the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note: Prerequisite: The DI/DO must be set as an output (p0728.8 = 1).
DI/DO: Bidirectional Digital Input/Output
p0728 CU, set input or output / CU DI or DO
CU_S Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: - Func. diagram: 1510, 2030,
2031, 2130, 2131, 2132, 2133
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
08 DI/DO 8 (X122.7/X121.7) Output Input -
09 DI/DO 9 (X122.8/X121.8) Output Input -
10 DI/DO 10 (X122.10/X121.10) Output Input -
11 DI/DO 11 (X122.11/X121.11) Output Input -
12 DI/DO 12 (X132.7) Output Input -
13 DI/DO 13 (X132.8) Output Input -
14 DI/DO 14 (X132.10) Output Input -
15 DI/DO 15 (X132.11) Output Input -
p0728 CX set input or output / CX DI or DO
CU_CX32 Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: - Func. diagram: 2230, 2231
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
08 DI/DO 8 (X122.7) Output Input -
09 DI/DO 9 (X122.8) Output Input -
10 DI/DO 10 (X122.10) Output Input -
11 DI/DO 11 (X122.11) Output Input -
p0738 BI: CU, signal source for terminal DI/DO 8 / CU S_src DI/DO 8
CU_S Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 1510, 2030,
2130
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0