Siemens SINAMICS S Series - p0211 Rated line freq; Rated line freq; p0220[0...1] Infeed line filter type; INF line filt type

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-116
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
- all of the components connected to this DC link must also be adapted to the low line supply voltage. It is especially
important that the rated DC voltage of all of the drives connected to this DC link is set with p0210 (e.g.
p0210(SERVO) = 1.35 * p0210(B_INF) = 310 V).
- it is not possible to use a Control Supply Module (CSM) to generate a 24 V supply from the DC link, as the mini-
mum, continuous DC link voltage may not lie below 430 V.
Note: The supply voltage range depends on the voltage class of the power unit.
400 V chassis units: 380 V <= p0210 <= 480 V
690 V chassis units: 500 V <= p0210 <= 690 V
400 V booksize units can also be connected to 3-ph. 230 V AC:
400 V booksize units: 200 V <= p210 <= 240 V or 380 V <= p0210 <= 480 V
Description: Sets the rated line frequency for the infeed.
Dependency: Refer to: p3409
Notice: For p3409 = 1, the following applies:
After operation has been enabled, the rated line supply frequency (p0211) is automatically set to a value of 50 Hz or
60 Hz corresponding to the currently measured frequency. This means that the parameter value of p0211 is, under
certain circumstances, changed.
For p3409 = 0, the following applies:
The system does not change parameter p0211.
Description: Sets the line filter type for the Active Line Module (ALM).
Using the line filter type, the filter capacitance (p0221), the filter resistance (p0222) and the inductance (p0223) and
the resistance (p0224) of the reactor are pre-assigned.
Values: 0: No line filter
1: Wideband Line Filter booksize 400 V 16 kW (6SL3000-0BE21-6AA0)
2: Wideband Line Filter booksize 400 V 36 kW (6SL3000-0BE23-6AA0)
3: Wideband Line Filter booksize 400 V 55 kW (6SL3000-0BE25-5AA0)
4: Wideband Line Filter booksize 400 V 80 kW (6SL3000-0BE28-0AA0)
5: Wideband Line Filter booksize 400 V 120 kW (6SL3000-0BE31-2AA0)
10: AIM F 400 V 132 kW 160 kW (6SL3300-7TE32-6Ax0)
11: AIM G 400 V 235 kW (6SL3300-7TE33-8Ax0)
12: AIM G 400 V 300 kW (6SL3300-7TE35-0Ax0)
13: AIM H 400 V 380 kW 500 kW (6SL3300-7TE38-4Ax0)
14: AIM J 400 V 630 kW 900 kW (6SL3300-7TE41-4Ax0)
15: AIM F 690 V 150 kW (6SL3300-7TH31-4Ax0)
16: AIM G 690 V 330 kW (6SL3300-7TH33-1Ax0)
17: AIM H 690 V 560 kW (6SL3300-7TH35-8Ax0)
18: AIM J 690 V 800 kW (6SL3300-7TH37-4Ax0)
19: AIM J 690 V 1100 kW 1400 kW (6SL3300-7TH41-3Ax0)
31: Basic Line Filter booksize 400 V 16 kW (6SL3000-0BE21-6DA0)
32: Basic Line Filter booksize 400 V 36 kW (6SL3000-0BE23-6DA0)
33: Basic Line Filter booksize 400 V 55 kW (6SL3000-0BE25-5DA0)
p0211 Rated line freq / Rated line freq
A_INF, S_INF Can be changed: T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8864, 8964
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
10 [Hz] 100 [Hz] 50 [Hz]
p0220[0...1] Infeed line filter type / INF line filt type
A_INF Can be changed: C2(1) Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: 8950
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 45 0

Table of Contents