Dependency: Refer to: p3665, r3666, p3667, p3668
Description: Setting of the temperature sensor for the Voltage Sensing Module (VSM).
The temperature sensor is connected to terminals X520.5 and X520.6 of the VSM.
Values: 0: No sensor
1: PTC
2: KTY84
Description: Displays the temperature actual value of a KTY84 temperature sensor connected to the Voltage Sensing Module
(VSM).
Prerequisite:
A KTY84 sensor is connected and p3665 is set to 2.
Dependency: Refer to: p3665
Note: For sensor type PTC (p3665 = 1), the following applies:
- below the nominal response temperature, r3666 = -50°C.
- above the nominal response temperature, r3666 = 199.9 °C.
Description: Displays the temperature actual value of a KTY84 temperature sensor connected to the Voltage Sensing Module
(VSM).
Prerequisite:
A KTY84 sensor is connected and p3665 is set to 2.
Dependency: Refer to: p3665
Note: For sensor type PTC (p3665 = 1), the following applies:
- below the nominal response temperature, r3666 = -50°C.
- above the nominal response temperature, r3666 = 199.9 °C.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Temperature alarm threshold exceeded Yes No -
01 Temperature fault threshold exceeded Yes No -
p3665[0...n] VSM temperature evaluation, sensor type / VSM TempSensorType
A_INF, S_INF, VEC-
TOR
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: p0140 Func. diagram: 9886
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 2 0
r3666 CO: VSM temperature KTY / VSM temp KTY
A_INF, S_INF Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9886
P-Group: Closed-loop control Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]
r3666[0...n] CO: VSM temperature KTY / VSM temp KTY
VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: p0150 Func. diagram: 9886
P-Group: Closed-loop control Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]