Description: Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from the speed/velocity limit (p1082) to zero within this time (if no initial rounding-off has
been activated).
Dependency: Refer to: p1030, p1047, p1082
Note: The deceleration time is extended corresponding to the activated initial rounding-off (p1030.2).
Description: Sets the effective setpoint after the internal motorized potentiometer ramp-function generator.
This setpoint is the output value of the motorized potentiometer and must be appropriately interconnected onwards
(e.g. with the main setpoint).
Recommend.: Interconnect the signal with main setpoint (p1070).
Dependency: Refer to: p1070
Note: For "With ramp-function generator", after an OFF1, OFF2, OFF3 or for a 0 signal via BI: p0852 (inhibit operation,
cancel pulses) the ramp-function generator output (r1050) is set to the starting value (configuration via p1030.0).
Description: Sets the effective setpoint after the internal motorized potentiometer ramp-function generator.
This setpoint is the output value of the motorized potentiometer and must be appropriately interconnected onwards
(e.g. with the main setpoint).
Recommend.: Interconnect the signal with main setpoint (p1070).
Dependency: Refer to: p1070
Note: For "With ramp-function generator", after an OFF1, OFF2, OFF3 or for a 0 signal via BI: p0852 (inhibit operation,
cancel pulses) the ramp-function generator output (r1050) is set to the starting value (configuration via p1030.0).
p1048[0...n] Motorized potentiometer ramp-down time / Mop ramp-down time
SERVO (Extended
setp), VECTOR
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3020
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 1000.000 [s] 10.000 [s]
r1050 CO: Motor. potentiometer setpoint after the ramp-function generator /
Mop setp after RFG
SERVO (Extended
setp), VECTOR
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 1550, 3020
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [RPM] - [RPM] - [RPM]
r1050 CO: Motor. potentiometer setpoint after the ramp-function generator /
Mop setp after RFG
SERVO (Extended
setp, Lin)
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 1550, 3020
P-Group: Setpoints Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [m/min] - [m/min] - [m/min]