List of parameters
Parameters
1-779
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the bidirectional digital inputs/outputs on the terminal module 41 (TM41) as input or output.
Description: Sets the bidirectional digital inputs/outputs on the terminal module 17 (TM17) as input or output.
Note: DI/DO: Bidirectional Digital Input/Output
Description: Sets the bidirectional digital inputs/outputs on the terminal module 15 (TM15) as input or output.
Bit field: Bit Signal name 1 signal 0 signal FP
08 DI/DO 8 (X541.2) Output Input -
09 DI/DO 9 (X541.3) Output Input -
10 DI/DO 10 (X541.4) Output Input -
11 DI/DO 11 (X541.5) Output Input -
p4028 TM41 set input or output / TM41 DI or DO
TM41 Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
08 DI/DO 0 (X521.1) Output Input 9661
09 DI/DO 1 (X521.2) Output Input 9661
10 DI/DO 2 (X521.3) Output Input 9662
11 DI/DO 3 (X521.4) Output Input 9662
p4028 TM17 set input or output / TM17 DI or DO
TM17 Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 Dynamic index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI/DO 0 (X520.2) Output Input -
01 DI/DO 1 (X520.3) Output Input -
02 DI/DO 2 (X520.5) Output Input -
03 DI/DO 3 (X520.6) Output Input -
04 DI/DO 4 (X520.8) Output Input -
05 DI/DO 5 (X520.9) Output Input -
06 DI/DO 6 (X521.2) Output Input -
07 DI/DO 7 (X521.3) Output Input -
08 DI/DO 8 (X521.8) Output Input -
09 DI/DO 9 (X521.9) Output Input -
10 DI/DO 10 (X522.2) Output Input -
11 DI/DO 11 (X522.3) Output Input -
12 DI/DO 12 (X522.5) Output Input -
13 DI/DO 13 (X522.6) Output Input -
14 DI/DO 14 (X522.8) Output Input -
15 DI/DO 15 (X522.9) Output Input -
p4028 TM15 set input or output / TM15 DI or DO
TM15 Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 Dynamic index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0000 bin

Table of Contents