List of parameters
Parameters
1-279
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Parameters p0100, p0205 (only for VECTOR) and the parameters of the basic drive commissioning (p0009) are not
reset (p0107, p0108, p0111, p0112, p0115, p0121, p0130, p0131, p0140, p0141, p0142, p0170, p0186 ... p0189).
These can only be reset using the factory setting of the complete drive unit (p0976).
Values: 0: Inactive
1: Starts a parameter reset
100: Starts a BICO interconnection reset
Note: A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Description: The parameter is used to initiate that the parameters are reset on Terminal Board 30 (TB30).
The sampling time p4099 is not reset if in so doing a conflict occurs with the basic clock cycle.
Parameter p0161 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Values: 0: Inactive
1: Starts a parameter reset
100: Starts a BICO interconnection reset
Note: A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Description: The parameter is used to initiate that the parameters are reset on Terminal Module 31 (TM31).
The sampling time p4099 is not reset if in so doing a conflict occurs with the basic clock cycle.
Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Values: 0: Inactive
1: Starts a parameter reset
100: Starts a BICO interconnection reset
Dependency: Refer to: p0010
Note: A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Description: The parameter is used to initiate that the parameters are reset on Terminal Module 41 (TM41).
Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
p0970 TB30 reset parameters / TB30 par reset
TB30 Can be changed: C2(30) Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Factory settings Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 100 0
p0970 TM31 reset parameters / TM31 par reset
TM31 Can be changed: C2(30) Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Factory settings Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 100 0
p0970 TM41 reset parameters / TM41 par reset
TM41 Can be changed: C2(30) Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Factory settings Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 100 0