List of parameters
Parameters
1-727
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the alarm threshold for the KTY temperature sensor of the Voltage Sensing Module (VSM) to monitor the line
filter temperature.
Prerequisite:
A KTY84 sensor is connected and p3665 is set to 2.
Dependency: Refer to: p3665
Refer to: F34207
Description: Sets the alarm threshold for the KTY temperature sensor of the Voltage Sensing Module (VSM) to monitor the line
filter temperature.
Prerequisite:
A KTY84 sensor is connected and p3665 is set to 2.
Dependency: Refer to: p3665
Refer to: F34207
Description: Sets the shutdown threshold for the KTY temperature sensor of the VSM to monitor the line filter temperature.
Dependency: Refer to: p3667
Refer to: A34211
Description: Sets the shutdown threshold for the KTY temperature sensor of the VSM to monitor the line filter temperature.
Dependency: Refer to: p3667
Refer to: A34211
p3667 VSM line filter overtemperature alarm threshold / VSMfilt_T A_thresh
A_INF, S_INF Can be changed: T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: 9886
P-Group: - Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [°C] 301 [°C] 150 [°C]
p3667[0...n] VSM line filter overtemperature alarm threshold / VSMfilt_T A_thresh
VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: p0150 Func. diagram: 9886
P-Group: - Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [°C] 301.00 [°C] 150.00 [°C]
p3668 VSM line filter overtemperature shutdown threshold / VSM filt_T F_thres
A_INF, S_INF Can be changed: T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: 9886
P-Group: - Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [°C] 301 [°C] 180 [°C]
p3668[0...n] VSM line filter overtemperature shutdown threshold / VSM filt_T F_thres
VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: p0150 Func. diagram: 9886
P-Group: - Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [°C] 301.00 [°C] 180.00 [°C]