EasyManua.ls Logo

Siemens SINAMICS S Series - A32414 (F, N) Encoder 2: Amplitude error track C or D (C^2 + D^2); N32415 (F, A) Encoder 2: Amplitude alarm track A or B (A^2 + B^2)

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of faults and alarms
Faults and Alarms
3-1673
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A32414 (F, N) Encoder 2: Amplitude error track C or D (C^2 + D^2)
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The amplitude (C^2 + D^2) of track C or D of the encoder or from the Hall signals, is not within the tolerance band-
width.
The nominal signal must be in the range 375 mV to 600 mV (500 mV -25 % / +20 %).
On the other hand, the response thresholds are < 230 mV and > 750 mV (frequency characteristic).
This fault also occurs if the A/D converter is overcontrolled.
If the amplitude is not within the tolerance bandwidth, then it cannot be used to initialize the start position.
Alarm value (r2124, interpret decimal):
Low word: Signal level, track C (16 bits with sign).
High word: Signal level, track D (16 bits with sign).
A signal level of 500 mV corresponds to the numerical value 5333 hex = 21299 dec.
Remedy: - check that the encoder cables are routed in compliance with EMC.
- check the plug connections.
- replace the encoder or encoder cable.
- check the Sensor Module (e.g. contacts).
- check the Hall sensor box
Reaction upon F: A_INFEED: NONE (OFF1, OFF2)
SERVO: NONE (IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
VECTOR: NONE (IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowl. upon F: IMMEDIATELY
Reaction upon N: NONE
Acknowl. upon N: NONE
N32415 (F, A) Encoder 2: Amplitude alarm track A or B (A^2 + B^2)
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The amplitude (A^2 + B^2) of track A or B is not within the tolerance bandwidth.
SMC20:
The nominal signal level is at 500 mV (500 mV -25 % / +20 %). The response threshold is < 300 mV.
SMC10:
The nominal signal level is at 2900 mV (2.0 Vrms). The response threshold is < 1414 mV (1.0 Vrms).
Alarm value (r2124, interpret decimal):
Low word:
Amplitude square root(A*A + B*B).
SMC20:
A signal level of 500 mV peak value corresponds to the numerical value 299A hex = 10650 dec.
SMC10:
A signal level of 2900 mV peak value corresponds to the numerical value 3333 hex = 13107 dec.
High word:
Angle 0 to 65535 corresponds to 0 to 360 degrees of the fine position. Zero degrees is at the negative zero crossover
of track B.
Remedy: - check the speed range, frequency characteristic (amplitude characteristic) of the measuring equipment is not suf-
ficient for the speed range.
- check that the encoder cables are routed in compliance with EMC.
- check the plug connections.
- replace the encoder or encoder cable.
- check the Sensor Module (e.g. contacts).
- dirty code disk
- aged lighting system.
Reaction upon F: A_INFEED: NONE (OFF1, OFF2)
SERVO: NONE (IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
VECTOR: NONE (IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowl. upon F: IMMEDIATELY
Reaction upon A: NONE
Acknowl. upon A: NONE

Table of Contents

Related product manuals