Parameters
List of parameters
1-844
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the edge status for digital input 8 ... 15 of terminal module 17 (TM17).
Assignment of the digital inputs to the bits:
DI 8: r4312.1 ... 0
DI 9: r4312.3 ... 2
DI 10: r4312.5 ... 4
DI 11: r4312.7 ... 6
DI 12: r4312.9 ... 8
DI 13: r4312.11 ... 10
DI 14: r4312.13 ... 12
DI 15: r4312.15 ... 14
Possible edge states:
Bit x, y = 0, 0 --> no edge detection
Bit x, y = 0, 1 --> 1st edge detected
Bit x, y = 1, 0 --> 2nd edge detected
Bit x, y = 1, 1 --> both edges detected
Note: DI: Digital input
Description: Displays the edge status for digital input 8 ... 15 of terminal module 15 (TM15).
Assignment of the digital inputs to the bits:
DI 8: r4312.1 ... 0
DI 9: r4312.3 ... 2
DI 10: r4312.5 ... 4
DI 11: r4312.7 ... 6
DI 12: r4312.9 ... 8
DI 13: r4312.11 ... 10
DI 14: r4312.13 ... 12
DI 15: r4312.15 ... 14
Possible edge states:
Bit x, y = 0, 0 --> no edge detection
Bit x, y = 0, 1 --> 1st edge detected
Bit x, y = 1, 0 --> 2nd edge detected
Bit x, y = 1, 1 --> both edges detected
Note: DI: Digital input
r4312 TM17 edge status digital input 8 ... 15 / TM17 EdgSt DI 8-15
TM17 Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
r4312 TM15 edge status digital input 8 ... 15 / TM15 EdgSt DI 8-15
TM15 Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -