List of faults and alarms
Faults and Alarms
3-1443
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
113: Write access only in the ready mode (p0010 = 0).
114: Write access only in the commissioning state, parameter reset (p0010 = 30).
115: Write access only in the Safety Integrated commissioning state (p0010 = 95).
116: Write access only in the commissioning state, technological application/units (p0010 = 5).
117: Write access only in the commissioning state (p0010 not equal to 0).
118: Write access only in the commissioning state, download (p0010 = 29).
119: Parameter may not be written into in download.
120: Write access only in the commissioning state – drive basis configuration (device: p0009 = 3).
121: Write access only in the commissioning state – define drive type (device: p0009 = 2).
122: Write access only in the commissioning state – data set basis configuration (device: p0009 = 4).
123: Write access only in the commissioning state – device configuration (device: p0009 = 1).
124: Write access only in the commissioning state – device download (device: p0009 = 29).
125: Write access only in the commissioning state – device parameter reset (device: p0009 = 30).
126: Write access only in the commissioning state – device ready (device: p0009 = 0).
127: Write access only in the commissioning state – device (device: p0009 not equal to 0).
129: Parameter may not be written into in download.
130: Transfer of the master control is inhibited via BI: p0806.
131: Required BICO interconnection not possible, because BICO output does not supply floating value
132: Free BICO interconnection inhibited via p0922.
133: Access method not defined.
200: Below the valid values.
201: Above the valid values.
202: Cannot be accessed from the Basic Operator Panel (BOP).
203: Cannot be read from the Basic Operator Panel (BOP).
204: Write access not permitted.
Remedy: - enter the correct value into the specified parameter.
- identify the parameter that narrows (restricts) the limits of the specified parameter.
F01043 Fatal error at project download
Drive object: All objects
Reaction: A_INFEED: OFF2 (OFF1)
SERVO: OFF2 (OFF1, OFF3)
VECTOR: OFF2 (OFF1, OFF3)
Acknowledge: IMMEDIATELY
Cause: A fatal error was detected when downloading a project using the commissioning (start-up) software.
Fault value (r0949, interpret decimal):
1: Device status cannot be changed to Device Download (drive object ON?).
2: Incorrect drive object number.
3: A drive object that has already been deleted is deleted again.
4: Deletes drive object that has already been registered for generation.
5: Deletes a drive object that no longer exists.
6: Generating an undeleted drive object that already existed.
7: Regeneration of a drive object already registered for generation.
8: Maximum number of drive objects that can be generated exceeded.
9: Error while generating a device drive object.
10: Error while generating target topology parameters (p9902 and p9903).
11: Error when generating a drive object (global component).
12: Error when generating a drive object (drive component).
13: Unknown drive object type.
14: Drive status cannot be changed to Ready (p0947 and p0949).
15: Drive status cannot be changed to Drive Download.
16: Device status cannot be changed to Ready.
17: It is not possible to download the topology. The component wiring should be checked, taking into account the
various messages/signals.
18: A new download is only possible if the factory settings are re-established for the drive unit.
19: The slot for the option module has been configured several times (e.g. CAN and COMM BOARD)
20: The configuration is inconsistent (e.g. CAN for Control Unit, however no CAN configured for drive objects A_INF,
SERVO or VECTOR ).