Siemens SINAMICS S Series - A07559 (F) Encoder 3: Reference point coordinate not in the permissible range; F07560 Drive encoder: Number of pulses is not to the power of two; F07561 Drive encoder: Number of multiturn pulses is not to the power of two; A07565 (F, N) Drive: Encoder error in PROFIdrive encoder interface 1

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of faults and alarms
Faults and Alarms
3-1563
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A07559 (F) Encoder 3: Reference point coordinate not in the permissible range
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The reference point coordinate received when adjusting the encoder via connector input CI:p2599 lies outside the
half of the encoder range and cannot be set as actual axis position.
Fault value (r0949, interpret decimal):
Limit value (absolute value) for the reference point coordinate.
Remedy: Set the reference point coordinate less than the limit value specified in the fault value.
See also: p2598 (EPOS reference point coordinate, signal source)
Reaction upon F: OFF1 (OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
F07560 Drive encoder: Number of pulses is not to the power of two
Drive object: SERVO, VECTOR
Reaction: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: For rotary absolute encoders, the pulse number in p0408 must be to the power of two.
Fault value (r0949, interpret decimal):
The fault value includes the encoder data set number involved.
Remedy: - check the parameterization (p0408, p0404.1, r0458.5).
- if required, upgrade the Sensor Module firmware.
F07561 Drive encoder: Number of multiturn pulses is not to the power of two
Drive object: SERVO, VECTOR
Reaction: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The multi-turn resolution in p0421 must be to the power of two.
Fault value (r0949, interpret decimal):
The fault value includes the encoder data set number involved.
Remedy: - check the parameterization (p0421, p0404.1, r0458.5).
- if required, upgrade the Sensor Module firmware.
A07565 (F, N) Drive: Encoder error in PROFIdrive encoder interface 1
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: An encoder error was signaled for encoder 1 via the PROFIdrive encoder interface (G1_ZSW.15).
Alarm value (r2124, interpret decimal):
Error code from G1_XIST2, refer to the description regarding r0483.
Note:
This alarm is only output if p0480[0] is not equal to zero.
Remedy: Acknowledge the encoder error using the encoder control word (G1_STW.15 = 1).
Reaction upon F: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
Reaction upon N: NONE
Acknowl. upon N: NONE
A07566 (F, N) Drive: Encoder error in PROFIdrive encoder interface 2
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: An encoder error was signaled for encoder 2 via the PROFIdrive encoder interface (G2_ZSW.15).
Alarm value (r2124, interpret decimal):
Error code from G2_XIST2, refer to the description regarding r0483.
This alarm is only output if p0480[1] is not equal to zero.