Parameters
List of parameters
1-590
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: Refer to: p2151, r2197, r2199
Description: Sets the signal source for the velocity setpoint 2.
The sum of CI: p2151 and CI: p2154 is used for the following messages/signals:
"Velocity setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
"Velocity setpoint - actual value deviation within tolerance t_on" (BO: r2199.4)
"Ramp-up/ramp-down completed" (BO: r2199.5)
Dependency: Refer to: p2151, r2197, r2199
Description: Sets the speed threshold value for the following messages:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency: Refer to: p2140, r2197
Description: Sets the velocity threshold value for the following messages:
"|v_act| < = velocity threshold value 2" (BO: r2197.1)
"|v_act| > velocity threshold value 2" (BO: r2197.2)
Dependency: Refer to: p2140, r2197
Description: Sets the switch-in delay time for the signal "comparison value reached" (BO: r2199.1).
Dependency: Refer to: p2141, p2142, r2199
p2154[0...n] CI: Velocity setpoint 2 / v_set 2
SERVO (Lin) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 8010
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p2155[0...n] Speed threshold 2 / n_thresh val 2
SERVO, VECTOR Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [RPM] 210000.00 [RPM] 900.00 [RPM]
p2155[0...n] Velocity threshold value 2 / v_thresh val 2
SERVO (Lin) Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [m/min] 1000.00 [m/min] 9.00 [m/min]
p2156[0...n] On delay, comparison value reached / t_on cmpr val rchd
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [ms] 10000.0 [ms] 0.0 [ms]