Siemens SINAMICS S Series - p0445[0...n] Encoder commissioning serial number part 5; Enc comm ser_no 5; p0446[0...n] Encoder SSI number of bits before the absolute value; Enc SSI bit before; p0447[0...n] Encoder SSI number of bits absolute value; Enc SSI bit val; p0448[0...n] Encoder SSI number of bits after the absolute value; Enc SSI bit after

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-183
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Serial number part 5 of the encoder for the commissioning.
Dependency: Refer to: p0440, p0441, p0442, p0443, p0444, r0460, r0461, r0462, r0463, r0464
Refer to: F07414
Note: A value of zero is displayed if an encoder is not present.
Description: Sets the number of bits before the absolute value in the SSI protocol.
Note: For example, error bit, alarm bit or parity bit can be positioned at these bits.
Description: Sets the number of bits for the absolute value in the SSI protocol.
Description: Sets the number of bits after the absolute value in the SSI protocol.
Note: For example, error bit, alarm bit or parity bit can be positioned at these bits.
Description: Sets the number of filler bits for double absolute value transfer in the SSI protocol.
Dependency: Refer to: p0429
p0445[0...n] Encoder commissioning serial number part 5 / Enc comm ser_no 5
SERVO, VECTOR Can be changed: C2(4) Calculated: CALC_MOD_ALL Access level: 4
Data type: Unsigned32 Dynamic index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
p0446[0...n] Encoder SSI number of bits before the absolute value / Enc SSI bit before
SERVO, VECTOR Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 65535 0
p0447[0...n] Encoder SSI number of bits absolute value / Enc SSI bit val
SERVO, VECTOR Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 65535 25
p0448[0...n] Encoder SSI number of bits after the absolute value / Enc SSI bit after
SERVO, VECTOR Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 65535 0
p0449[0...n] Encoder SSI number of bits, filler bits / Enc SSI fill bits
SERVO, VECTOR Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 65535 1