Figure 2-228 8826 – Status word sequence control infeed
- 8826 -
Function diagram
87654321
fp_8826_01_eng.vsd
DO: S_INF
SINAMICS S
19.02.07 V02.05.00
Smart Infeed - Status word, sequence control infeed
[8832] From sequence control
[8832] From sequence control
[8832] From sequence control
[8832] From sequence control
[8832] From sequence control
[8850] From power unit
[8834.4] From line contactor control
r0899.0
r0899.1
r0899.2
r0899.4
r0899.6
r0899.11
r0899.12
r0899.9
r0899
ZSW sequence ctrl
<1> The master system requests process data.
Bit 9 = 1 --> Ready to exchange process data
11
12
13
14
15
Bit
No.
10
9
8
7
6
5
4
3
0
1
2
1 = Ready to operate
1 = Ready to power-up
Status word sequence control infeed
1 = Operation enabled
Reserved
1 = No OFF2 active
1 = Power-on inhibit
Reserved
Reserved
1 = Control requested
Reserved
1 = Pre-charging completed
1 = Line contactor closed
Reserved
Reserved
Reserved
Reserved
<1>
p0115[3] (2000.00 µs)
[8864.5]