Parameters
List of parameters
1-36
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
95: Safety Integrated
98: Command Data Sets (CDS)
99: Drive Data Sets (DDS)
Dependency: Refer to: p0003
Note: Example:
p0004 = 3: Only the parameters for the motor are displayed.
Description: Sets the parameter number and parameter index for display for p0006 = 2, 4 for the Basic Operator Panel (BOP).
Examples for the SERVO drive object:
p0005 = 21: Speed actual value smoothed (r0021)
p0005 = 25: Drive output voltage smoothed (r0025)
p0005 = 26: Speed actual value smoothed (r0026)
p0005 = 27: Absolute current actual value, smoothed (r0027)
Index: [0] = Parameter number
[1] = Parameter index
Dependency: Refer to: p0006
Note: Procedure:
1.
The parameter number to be displayed should be set in index 0. Only the monitoring parameters (only read param-
eters) can be set, that actually exist for the actual drive object.
If the set parameter number is not indexed, or if there is an index in index 1 that lies outside the valid range of the
set parameter, then index 1 is automatically set to 0.
2.
The index that belongs to the parameter set in index 0 should be set in index 1. The permissible changes in index 1
always depend on the parameter number set in index 0.
Description: Sets the mode of the operating display for the Basic Operator Panel (BOP) in the operating states "ready" and
"operation".
Values: 4: p0005
Dependency: Refer to: p0005
Note: Mode 0 ... 3 can only be selected if also r0020, r0021 are available on the drive object.
Mode 4 is available for all drive objects.
p0005[0...1] BOP operating display selection / BOP op_disp sel
A_INF, B_INF,
CU_S, DMC20,
SERVO, S_INF,
TB30, TM15,
TM15DI_DO, TM17,
TM31, TM41,
TM54F_MA,
TM54F_SL, VEC-
TOR
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 65535 [0] 2
[1] 0
p0006 BOP operating display mode / BOP op_ disp mode
CU_S, DMC20,
TB30, TM15,
TM15DI_DO, TM17,
TM31, TM41,
TM54F_MA,
TM54F_SL
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
4 4 4