Description: Displays the stator flux of the identified saturation characteristic.
The values are referred to the stator flux at the magnetizing current (r0331).
Dependency: Refer to: p1959, p1960, r1962
Note: The saturation characteristic consists of the value pairs from p1962 and p1963 with the same index.
Description: Displays the magnetizing inductances of the identified saturation characteristic.
The values are referred to r0382.
Index: [0] = Value 1
[1] = Value 2
[2] = Value 3
[3] = Value 4
[4] = Value 5
Dependency: Refer to: r0382
Description: Displays the rotor flux values of the identified saturation characteristic.
After they have been determined, the values are transferred to p0362 ... p0365.
Index: [0] = Value 1
[1] = Value 2
[2] = Value 3
[3] = Value 4
[4] = Value 5
Description: Sets the speed for the identification of the moment of inertia and the vibration test.
Induction motor:
r1963[0...9] Saturation characteristic stator flux identified / Sat_char flux
SERVO Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r1963[0...4] Saturation characteristic, magnetizing inductance / Sat_char L_main
VECTOR (n/M) Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r1964[0...4] Saturation characteristic, rotor flux / Sat_char rot flux
VECTOR (n/M) Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p1965 Speed_ctrl_opt speed / n_opt speed
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
10 [%] 75 [%] 40 [%]