Parameters
List of parameters
1-460
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the control word for the excitation equipment.
Description: Displays the status word of the excitation equipment.
Dependency: Refer to: p1645
Description: Displays the torque generating current setpoint Iqset after the torque limits and the clock cycle interpolation is front
of the current setpoint filters.
Description: Displays the force generating current setpoint Iqset after the force limits and the clock cycle interpolation is front of
the current setpoint filters.
r1648.0...10 CO/BO: Excitation, control word / Excitation STW
VECTOR (n/M) Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 6495, 6497
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Power-up excitation Yes No -
01 Excitation no OFF2 Yes No -
02 Excitation no OFF3 Yes No -
03 Enable excitation operation Yes No -
07 Excitation acknowledge fault Yes No -
10 Master control by excitation equipment Yes No -
r1649.0...7 CO/BO: Excitation status word / Excitation ZSW
VECTOR (n/M) Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 6495, 6497
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Excitation ready to be powered-up, feed-
back signal
Yes No -
01 Excitation ready feedback signal Yes No -
02 Excitation in operation feedback signal Yes No -
03 Excitation group signal fault Yes No -
07 Excitation, group signal alarm Yes No -
r1650 Current setpoint torque-generating before filter / Iq_set before filt
SERVO, VECTOR
(n/M)
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 5710
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r1650 Current setpoint force-generating before filter / Iq_set before filt
SERVO (Lin) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 5710
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]